ADVANTECH ADAM-5018P-AE 7-ch Thermocouple Input Module with Independent Input Range

  • High Common Mode: 2000 VDC
  • Fault and Overvoltage Protection: Withstands over voltage up to ±35 V
  • Isolation Voltage: 3,000 VDC
  • Filter function: Yes
  • Built-in TVS/ESD Protection
  • Input Impedance: 20 MΩ. (Build-in 120 Ω Register for Current Input) with Channels: 7 differential with Independent Input Range
  • CMR @ 50/60 Hz: 92 dB min
  • Sampling Rate: 10 samples/sec. (total)
  • Accuracy Bandwidth: ±0.1% or better, 13.1 Hz @ 50 Hz, 15.72 Hz @ 60 Hz
Deskripsi
Category Attribute Value
General Connectors 1 x 16-pin plug-in screw terminal
General Humidity (Operating) 5~95% RH (non-condensing)
General Humidity (Storage) 5~95% RH (non-condensing)
Hardware Certification CE, FCC class A
Thermocouple Input Channels 7
Thermocouple Input Input Impedance 2 MΩ
Thermocouple Input Input Type mA, mV, V, T/C: J, K, T, E, R, S, B type
Thermocouple Input Resolution 16-bit
Thermocouple Input Sample Range 10 S/s (sum)
Thermocouple Input Temperature Range Type J (0~760° C), Type K (0~1370° C), Type T (-100~400° C), Type E (0~1000° C), Type R (500~1750° C), Type S (500~1750° C), Type B (500~1800° C)
Thermocouple Input Voltage Range ±15 mV (0.2%), ±50 mV, ±100 mV, ±500 mV ±1 V, ±2.5 V

Datasheet

Informasi Tambahan
Brand

Advantech